Overview
Bus Connections and Termination
The H7506 supports connections between single-channel PES and redundant PES H41q/H51q systems through the BV 7040 and BV 7046 data cables.
The terminal provides the following connection features:
- 25-pole Min-D socket: Connects the PES systems through compatible data cables.
- Two 6-pole plug clamps: Provide connection points for the 2-wire bus.
- Two termination switches: Allow activation of the bus terminating resistors at each end of the 2-wire bus.
Meanwhile, correct termination helps control signal reflections on the bus. Technicians can use the built-in switches to configure termination according to the terminal’s position in the bus wiring.
Transmission Distance
The maximum transmission length depends on the conductor cross-section:
- 1200 m: With a wiring cross-section of 0.25 mm2.
- 2400 m: With a wiring cross-section of 0.5 mm2.
The specified loop resistance is 180 Ohm. Therefore, wiring cross-section and loop resistance should be considered when checking the communication cable requirements.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | H7506 |
| Brand | HIMA |
| Product Type | DIN Mount Bus Terminal |
| Device Type | Bus Terminal |
| PES Connection | 25-pole Min-D socket |
| Compatible PES Configurations | Single-channel PES; redundant PES H41q/H51q |
| Data Cable Types | BV 7040, BV 7046 |
| Bus Connection | Two 6-pole plug clamps |
| Bus Configuration | 2-wire bus |
| Bus Termination | Two switches for terminating resistors |
| Maximum Transmission Length | 1200 m at 0.25 mm2; 2400 m at 0.5 mm2 |
| Loop Resistance | 180 Ohm |
| Dimensions | 5.1 x 12.7 x 5.1 cm |
| Estimated Shipping Size | 11 x 4 x 5.5 cm |
| Weight | 0.5 kg |
| Country of Origin | Germany |
| Manufacturer | HIMA |
Frequently Asked Questions
Q: Which HIMA systems can connect to the H7506?
A: The H7506 supports single-channel PES and redundant PES H41q/H51q connections through BV 7040 and BV 7046 data cables.
Q: How do the bus termination switches work?
A: The two switches activate the bus terminating resistors. They allow technicians to configure termination at either end of the 2-wire bus.
Q: What is the maximum transmission distance of the H7506?
A: The maximum specified distance is 1200 m with 0.25 mm2 wiring or 2400 m with 0.5 mm2 wiring.