Overview
Functional Configuration
The F35 011 30 combines digital output control with counter input functions. Its two counters each provide 3 inputs, allowing the module to process pulse signals for counting operations.
In addition, the 8 output channels support connected control circuits with a minimum load of 2 mA per channel. The specified output voltage drop and internal power dissipation provide useful reference values when checking connected loads.
Counter Input Characteristics
The module supports pulse measurement with a 24-bit counter resolution and a maximum input frequency of 100 kHz. Its minimum pulse length is 5 us, which defines an important signal timing condition when selecting connected pulse sources.
Furthermore, the input line length can reach 500 m under the specified configuration. Input current varies with the applied voltage, so the 5 V and 24 V operating conditions should be considered when checking signal interfaces.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | HIMatrix F35 011 30 |
| Spare Model | HIMatrix F3501130 |
| Brand | HIMA |
| Product Type | Safety-Related Controller Module |
| Number of Outputs | 8 |
| Minimum Output Load | 2 mA per channel |
| Output Voltage L+ Minus | 2 V |
| Maximum Internal Voltage Drop | 2 W at 2 A |
| Number of Counters | 2 |
| Counter Inputs | 3 per counter |
| Input Current | 1.4 mA at 5 V; 6.5 mA at 24 V |
| Input Impedance | 3.7 kOhm |
| Maximum Input Line Length | 500 m |
| Counter Resolution | 24 bit |
| Minimum Pulse Length | 5 us |
| Maximum Input Frequency | 100 kHz |
| Manufacturer | HIMA |
| Country of Origin | Germany |
| Weight | 1.2 kg |
| Estimated Shipping Size | 25.5 x 8 x 11.3 cm |
| HS Code | 8537101190 |
Frequently Asked Questions
Q: How many output channels does the HIMA F35 011 30 provide?
A: The module provides 8 output channels. Each channel has a specified minimum load of 2 mA.
Q: How many counter functions are available?
A: The F35 011 30 has 2 counters, each with 3 inputs. The counters provide 24-bit resolution and support input frequencies up to 100 kHz.
Q: What pulse signals can the counter inputs process?
A: The specified minimum pulse length is 5 us, and the maximum input frequency is 100 kHz. Check these limits against the pulse source specifications when selecting the input signal.
















Reviews