Overview
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | SE4302T02 |
| Brand | Emerson |
| Product Type | Discrete Output CHARM |
| System Platform | DeltaV Distributed Control System |
| Module Function | 24 VDC isolated digital output |
| Output Type | Inductive load switching |
| Output Range | 4 VDC to 32 VDC |
| Output Rating | 1.0 A continuous, 2 A inrush for less than 100 ms |
| Off-State Leakage Current | 1 mA maximum |
| Output Behavior | Configurable momentary output and continuous pulse output |
| Isolation Type | Galvanic isolation |
| Isolation Test Level | 1000 VDC factory tested |
| Channel Configuration | Individually configured and electronically keyed |
| Model | SE4302T02 |
| Brand | Emerson |
| Origin | USA |
Channel-to-Channel Isolation and HART Process Control Compatibility
The SE4302T02 applies Emerson DeltaV CHARM technology to provide isolated digital output control between the system I/O layer and field devices. The module uses galvanic isolation to separate output circuits and reduce electrical interaction between channels.
Additionally, the DeltaV electronic marshalling architecture allows channel-level configuration without traditional cabinet-level rewiring. The isolated output design supports direct switching of 24 VDC inductive loads, while configured pulse and momentary modes allow application-specific actuator control.
Frequently Asked Questions
Q: What type of field devices can the SE4302T02 control?
A: The module controls 24 VDC inductive loads through discrete output channels. Typical connections include solenoid valves, relays, and similar switching devices within the specified output range.
Q: Does the SE4302T02 provide electrical isolation between output channels?
A: Yes. The module provides galvanic isolation, and the isolation performance is factory tested to 1000 VDC.
Q: Can the output behavior be configured for different control actions?
A: Yes. The module supports configurable momentary output and continuous pulse output operation through DeltaV system configuration.
Field Installation Guidelines
- Install the SE4302T02 on a compatible DeltaV CHARM baseplate assembly according to Emerson installation documentation.
- Verify the field wiring polarity before connecting 24 VDC output devices.
- Separate low-level signal wiring from high-current inductive load wiring where possible.
- Connect cable shields according to the plant grounding standard to reduce electrical interference.
- Confirm load current requirements remain within the specified continuous and inrush output ratings.
- Inspect terminal connections for proper mechanical tightening before system commissioning.
- Configure channel parameters in the DeltaV engineering environment before enabling field outputs.
Emerson Top Products
| Emerson DeltaV | Epro | Ovation/Westinghouse |
| KJ1501X1-BC3 | 9100-00049-03 | 1C31122G01 |
| KJ3202X1-BA1 | A6110 | 1C31125G03 |
| KJ3222X1-BA1 | A6120 | 1C31232G01 |
| KJ3243X1-BA1 | A6125 | 1C31147G01 |
| KJ3002X1-BG1 | A6140 | 1B30035H01 |
| KJ3002X1-BB1 | A6210 | 1B30023H02 |
| KJ3001X1-BB1 | A6220 | 1B30023H01 |
| KJ3002X1-BC1 | A6312 | 1C31132G01 |
| KJ3002X1-BF1 | A6312/06 | 1C31129G03 |
| KJ3001X1-BJ1 | A6312/08 | 5X00119G01 |
Customers Also Viewed
| Bently Nevada | ABB | Yokogawa | Woodward | Schneider |
| 133835-02 | SPDSM04 | CP451-10 | 5463-785 | 140CPU65150 |
| 135321-01 | SPIEET800 | CP461 | 5437-672 | BMEXBP0400 |
| 135322-01 | SPINIET800 | CP461-50 | 9907-175 | 140CPU67160 |
| 136751-01 | SPNLK01 | CP451-11 | 5466-355 | 170FNT11001 |
| 136751-02 | SPSED01 | CP701 S1 | 5466-257 | 170ADO34000 |
| 184139-10 | SPSEM11 | CP345 S1 | 5466-1049 | 170ADM35010 |
| 82362-01 | SPSET01 | SCP461-11 S1 | 5501-381 | 170ADI34000 |
| 84134-01 | SPTKM01 | CP451-10 S2 | 8200-177 | 140ARI03010 |
| 87900-02 | SPTPS02 | CP401-10 | 8200-205 | BMXCPS4002 |
| 89998-01 | SPTPS13 | NFCP100-S00 | 9907-029 | 140CRP93200 |














Reviews
There are no reviews yet.