Overview
Output Functions
The ADV551-P63/D5A00 supports three output functions:
- Status output: Provides ON/OFF status signals with a response time of 3 ms or less.
- Pulse width output: Generates one-shot pulses with adjustable widths from 8 ms to 7200 s.
- Time-proportional output: Controls ON/OFF output timing according to the configured time-proportioning function.
In addition, the module supports mixed status and pulse outputs, with a response time of 10 ms or less. Pulse width resolution is 8 ms, with an additional ON/OFF delay of up to 1 ms.
Electrical Characteristics
The module provides 32 current-sink output channels, each rated for a maximum load current of 100 mA at 26.4 VDC. The maximum ON-state output voltage is 2 VDC, while the maximum OFF-state leakage current is 0.1 mA.
Furthermore, the external power supply operates within a voltage range of 20.4 to 26.4 VDC. These electrical limits help users check field-device requirements and output load conditions before installation.
Connection and Configuration
The D5A00 option includes a KS Cable Interface Adapter for 32-channel digital output connections, model ATD5A-00. The module supports pressure clamp terminals, dedicated AKB331 cables, and MIL connector cables.
For the P63 configuration, the suffix codes specify the following features:
- P: Pulse width output and time-proportional output functions.
- 6: Status display, without explosion protection.
- 3: ISA Standard G3 option and operating temperature option of -20 to 70 deg C.
- D5A00: KS Cable Interface Adapter for 32-channel digital connections, model ATD5A-00.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | ADV551-P63/D5A00 |
| Brand | Yokogawa |
| Product Type | Digital Output Module |
| Number of Output Channels | 32 |
| Rated Applied Voltage | 24 VDC |
| Output Format | Current sink |
| Maximum Load Current | 100 mA/channel at 26.4 VDC |
| Output ON Voltage | 2 VDC maximum |
| OFF-State Leakage Current | 0.1 mA maximum |
| External Power Supply Rating | 24 VDC, 50 mA |
| External Power Supply Voltage Range | 20.4 to 26.4 VDC |
| Withstanding Voltage | 2 kV AC for 1 minute between output signal and system |
| Withstanding Voltage Between Commons | 500 V AC for 1 minute |
| Common Configuration | Common minus (-) side for every 16 channels |
| Status Output Response Time | 3 ms or less |
| Mixed Status and Pulse Output Response Time | 10 ms or less |
| Pulse Width | 8 ms to 7200 s |
| Pulse Width Resolution | 8 ms |
| Additional ON/OFF Delay | 1 ms maximum |
| Output Functions | Status output, one-shot pulse width output, time-proportioning output |
| Maximum Current Consumption | 700 mA at 5 VDC |
| External Power Supply Current Consumption | 60 mA |
| Connection Adapter | ATD5A-00 |
| External Connection | Pressure clamp terminal, AKB331 dedicated cable, MIL connector cable |
| Weight | Approx. 0.20 kg |
Frequently Asked Questions
Q: What output functions does the ADV551-P63/D5A00 support?
A: It supports ON/OFF status output, one-shot pulse width output, and time-proportional output. The P suffix identifies the pulse width and time-proportional output configuration.
Q: Which cable interface adapter is included with this model?
A: The D5A00 option specifies the KS Cable Interface Adapter ATD5A-00 for 32-channel digital connections. The module also supports dedicated AKB331 cables and MIL connector cables.
Q: Does the ADV551-P63/D5A00 have explosion protection?
A: No. The suffix code 6 specifies status display without explosion protection. However, the suffix code 3 includes the ISA Standard G3 option and the -20 to 70 deg C temperature option.