Overview
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | K9203A |
| Brand | HIMA |
| Product Parameters | Circulation Fan Drawer |
| Replaces | K 9202 (3-axis circulation fan drawer) |
| Tariff Code | 8537101190 |
| Country of Origin | Germany |
| Estimated Shipping Size | 48.3 x 20.3 x 4.5 cm |
| Weight | 2 kg |
| Material | Aluminum, anodized |
| Operating Data | 24 VDC, -15 to +20 %, ripple ≤15 % |
| Air Flow | 300 m3 per hour |
| Rated Speed | 2800 min^-1 |
| Sound Pressure Level | approx. 55 dB(A) |
| Lifetime at 40 °C | 62 500 h |
| Space Requirement | 19 inch, 1 RU, depth 215 mm |
| Ambient Temperature | -20 to +70 °C |
The 24 VDC operating range allows a -15 % to +20 % supply deviation, while the ripple limit of ≤15 % keeps motor stress low on shared DC bus supplies. Therefore, the drawer runs from a standard controlled 24 VDC rack power feed without extra conditioning. The run monitor observes fan operation and supports status feedback; however, the original data does not define its alarm outputs or interface signals.
At 2800 min^-1, the unit delivers 300 m3 per hour of airflow and stays near 55 dB(A) sound pressure. Meanwhile, the rated lifetime of 62 500 h at 40 °C reflects continuous-duty bearing and motor endurance, not a service interval under all ambient conditions. Furthermore, the 1 RU, 19-inch form factor with 215 mm depth lets maintenance teams swap the drawer into existing racks without modifying panel cutouts.
Frequently Asked Questions
Q: What does the K9203A replace?
A: It replaces the earlier 3-axis circulation fan drawer listed under K 9202. Use K9203A as the current order number when sourcing a replacement.
Q: Can the K9203A share a 24 VDC supply with other rack components?
A: Yes, provided the supply stays within -15 % to +20 % of 24 VDC and ripple stays ≤15 %. Size the power budget for continuous fan load plus existing rack loads.
Q: Does the run monitor provide a dry contact or digital alarm?
A: The provided data confirms a run monitor is present but does not specify contact type, signal level, or wiring. Verify the monitor interface against the unit label or HIMA rack documentation before termination.

















Reviews
There are no reviews yet.