Overview
I/O Configuration
The module combines analog input and output functions in one remote I/O device. The eight analog inputs acquire field measurement signals, while the four analog outputs provide non-safety-related analog signal outputs. This configuration allows input monitoring and output control through a single device.
Analog Signal Characteristics
The input channels support voltage and current measurement. In addition, the input range includes 0 to 10 VDC and 0/4 to 20 mA using a 500 ohm shunt. The module provides 12-bit resolution, allowing the controller to process measured analog values for monitoring and safety-related functions.
ManualsLib+1
The four analog outputs provide a 0 to 20 mA output range. However, these outputs are not inherently safety-related. Therefore, applications requiring a safety-related output function must use output readback through safety-related analog inputs and evaluate the values in the user program.
ManualsLib
Communication and Diagnostics
The F3 AIO 8/4 01 communicates with its associated controller through HIMA SafeEthernet. It has two RJ45 Ethernet ports with an integrated switch and supports 10/100Base-T communication. Furthermore, front-panel LED indicators show operating voltage, system status and communication status. Maintenance personnel can also access diagnostic history through the programming tool.
ManualsLib+1
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | F3AIO8/401 |
| Brand | HIMA |
| Product Type | Analog I/O Remote Module |
| Product Series | HIMatrix F3 |
| Analog Input Channels | 8 |
| Analog Output Channels | 4 |
| Analog Input Range | 0 to 10 VDC; 0/4 to 20 mA |
| Analog Input Resolution | 12-bit |
| Analog Input Shunt | 500 ohm |
| Analog Output Range | 0 to 20 mA |
| Output Safety Classification | Non-safety-related |
| Power Supply | 24 VDC |
| Operating Voltage Tolerance | -15% to +20% |
| Current Consumption | Approx. 0.4 A idle; max. 0.8 A |
| Communication Interface | 2 x RJ45 Ethernet |
| Communication Protocol | SafeEthernet |
| Ethernet Speed | 10/100Base-T |
| Response Time | 20 ms or greater |
| Operating Temperature | 0 to +60 deg C |
| Storage Temperature | -40 to +85 deg C |
| Protection Rating | IP20 |
| Dimensions (W x H x D) | 207 x 114 x 97 mm |
| Weight | Approx. 0.95 kg |
ManualsLib+2
Frequently Asked Questions
Q: Are all four analog outputs safety-related?
A: No. The four analog outputs are non-safety-related by default. For safety-related output applications, the output values must be read back through safety-related analog inputs and evaluated in the user program.
Q: Which communication protocol does the F3AIO8/401 use?
A: It communicates with the associated HIMA controller through SafeEthernet using two RJ45 Ethernet ports. Modbus TCP/IP is not confirmed as a supported protocol for this model.
Q: Can the module operate independently?
A: No. The F3 AIO 8/4 01 operates together with an associated controller and requires the appropriate system configuration and programming tools.